dc.description.abstract© 2020 IEEE. Recently, distance relays are used in conventional protection to protect the transmission system, which consists of primary and back up protections. However, the primary protection used in traditional protection cannot be designed to cover the entire length of the transmission line. Moreover, the rapid increase in distributed generations (DGs) connected to the transmission line may increase fault impedance seen through distance relay. It results in an under-reach and miscoordination problem due to incorrect impedance calculation. In this paper, the development of distance relay based on Wide-Area Protection (WAP) for transmission systems is presented. The proposed method enjoins to instantly collect information of the distance relay and the circuit breaker status in local substations and nearby substations. The simulation is developed by using the DigSILENT PowerFactory program. The results present that the proposed method can improve the stability and reliability of the protection system and overcome such a problem.en_US
dc.subjectComputer Scienceen_US
dc.subjectDecision Sciencesen_US
dc.subjectEnergyen_US
dc.subjectEngineeringen_US
dc.subjectMathematicsen_US
dc.titleDevelopment of distance relay based on wide-area protection for transmission systems of provincial electricity authorityen_US
dc.typeConference Proceedingen_US
article.title.sourcetitleSEST 2020 - 3rd International Conference on Smart Energy Systems and Technologiesen_US
article.stream.affiliationsChiang Mai Universityen_US
article.stream.affiliationsProvincial Electricity Authority (PEA)en_US
Appears in Collections:CMUL: Journal Articles

Files in This Item:
There are no files associated with this item.


Items in CMUIR are protected by copyright, with all rights reserved, unless otherwise indicated.