Please use this identifier to cite or link to this item: http://cmuir.cmu.ac.th/jspui/handle/6653943832/59543
Title: Investigation of single phase reclosing using arc model on the 500 kV transmission line from Mae Moh to Tha Ta Ko
Authors: K. Ngamsanroaj
S. Premrudeepreechacharn
Authors: K. Ngamsanroaj
S. Premrudeepreechacharn
Keywords: Energy
Issue Date: 27-Aug-2009
Abstract: Single phase switching has become an increasingly more viable approach to the operation of EHV systems in recent years. Indeed, single phase reclosing, if successful, represents a significant step in improving system performance and is an attractive, economical means of obtaining acceptable transient stability with fewer lines. Single phase reclosing has the additional benefits of reducing switching overvoltages. This paper addresses the investigation of single phase reclosing using arc model on the on single and double circuit transmission line employing single phase switching due to single line to ground faults The work is performed by EMTP on the Thailand 500 kV transmission line from Mae Moh to Tha Ta Ko. A series of studies have been performed. © 2009 IEEE.
URI: https://www.scopus.com/inward/record.uri?partnerID=HzOxMe3b&scp=84869980859&origin=inward
http://cmuir.cmu.ac.th/jspui/handle/6653943832/59543
ISSN: 21574847
21574839
Appears in Collections:CMUL: Journal Articles

Files in This Item:
There are no files associated with this item.


Items in CMUIR are protected by copyright, with all rights reserved, unless otherwise indicated.